Appearance
Chapter 10 — Multiconductor lines: sequence data and modal decomposition
Real transmission lines carry three phases on the same towers, close enough that each conductor's magnetic and electric field reaches the other two. Current in phase A induces voltage along phases B and C; charge on A raises the potential of B and C. The single-conductor model of Chapters 8 and 9 has nothing to say about any of it.
The remedy is one of the most elegant ideas in power-system analysis. Rather than build a coupled three-conductor wave model from first principles, we change coordinates: we find a set of combinations of the three phases that do not interact, solve each as an ordinary Chapter 8 line, and transform back. This chapter derives those coordinates, shows why the balanced case collapses to a familiar transformation, and connects the result to the three ways NumaSim accepts three-phase line data.
Learning objectives
By the end of this chapter you should be able to:
- Write the multiconductor line equations and identify what the coupling terms do.
- Explain how a modal transformation turns
coupled lines into independent ones. - Derive the balanced-line modes and relate them to Clarke components and to sequence quantities.
- Explain physically why the ground mode is slower and higher-impedance than the aerial modes.
- Choose among sequence, sequence-RLC, and balanced-matrix data entry, and convert between them.
10.1 Three conductors, one coupled problem
Repeat the slice argument of Chapter 8 with three conductors instead of one. The voltages and currents become vectors, and the per-unit-length parameters become matrices:
where
Repeating the derivation of Chapter 8, differentiation and substitution give
which resembles the scalar wave equation with
10.2 Changing coordinates: modal decomposition
The way forward is to abandon phase quantities as the working variables. The matrix
where the columns of
and because
This constitutes a complete algorithm, and it is the one NumaSim implements:
One caveat attaches to this, and it is the reason Chapter 11 exists. In general
10.3 The balanced line and Clarke components
For a line that is fully transposed — each conductor spends a third of the route in each physical position — all three conductors are electrically identical and all three pairs are coupled identically. Every matrix in the problem then has the same simple shape: equal diagonals and equal off-diagonals.
Matrices of this form have eigenvectors that can be written down without knowing
- The direction
, with eigenvalue . All three conductors carry the same current in the same direction. - Everything orthogonal to it — a two-dimensional space, so a repeated eigenvalue
. The three currents sum to zero.
A convenient orthonormal choice of eigenvectors is Clarke's:
This matrix is real, constant, orthogonal (
What the two mode types physically are
The distinction between the mode types is not a mathematical accident. It is a question of where the current returns.
In an aerial mode the three currents sum to zero, so the outgoing and returning paths are conductors a few metres apart. The enclosed loop is small, making the inductance small, and the conductors are close, making the capacitance large. The consequence is a low surge impedance and propagation at nearly the speed of light.
In the ground mode all three currents flow in the same direction and return through the earth, tens of metres below and spread over a large, poorly conducting volume. The loop is very much larger, so the inductance is greater, and the effective separation is larger, so the capacitance is smaller. The consequence is
The ground mode is therefore slower and stiffer. On a typical overhead line
Modes and sequence components
The resemblance between the aerial/ground split and positive- and zero-sequence impedances is not a coincidence, since both arise from diagonalizing the same balanced matrix. The
10.4 Entering three-phase line data
Setting the Model's Conductors to 3 reveals the three-phase entry methods. All three ultimately produce the same six numbers —
Bergeron — Sequence Surge Impedance takes the modal quantities directly: Z1, τ1, Z0, τ0. It is the appropriate choice when the available data is in surge-impedance form, or when direct control over the arrival times is wanted. Internally,
Note that this method provides no way to specify resistance; it describes a lossless line.
Bergeron — Sequence RLC takes a Length plus per-kilometre
Bergeron — Balanced Matrix takes a Length plus the self and mutual values directly:
The capacitance formulas carry the opposite sign pattern to the inductance ones because the mutual entry in a nodal capacitance matrix is negative.
The last equality deserves attention: mutual resistance is not modelled, so matrix entry forces
Each of these methods has a PI — counterpart for short lines, which follows Chapter 9's rules.
10.5 What the engine does with three phases
The three-phase travelling-wave line splits into two halves exactly as the single-phase one does, but each half now presents a
which NumaSim realizes without ever forming the matrix: a conductance
The history side keeps the two mode families separate, each with its own integer delay from Chapter 9:
The fallback test of Chapter 9 is all-or-nothing: the line is demoted to a
Limits worth knowing
- One or three conductors. There is no six-conductor double-circuit model, and earth wires cannot be entered as extra conductors; they must be folded into the sequence data beforehand (Chapter 12).
- Balanced only. Matrix entry asks for a single
and a single , so an untransposed line, in which the three phases genuinely differ, cannot be represented. Most studies use transposed data in any case. - No mutual resistance, as noted above.
- Constant parameters.
, , , do not vary with frequency. The consequences are Chapter 11's subject.
10.6 Lab: two modes, two arrival times
Open the AC line fault demo in simulator →
A 230 kV source feeds a three-phase travelling-wave line into a
with
What makes this lab work is the choice of observation point. The fault is at the receiving end, but the currents plotted, Ia, Ib and Ic, are measured at the source, a full line length away. Nothing at the source can react to the fault until a wave has crossed the line, so the sending end acts as a modal stopwatch from which the travel times can be read directly.
Consider first what that stopwatch should read.
Run the sample as shipped, with the fault type set to ABC-G, a symmetrical three-phase fault. Zoom the plot tightly into the first
- The currents follow their pre-fault trend undisturbed until the fifth step and then break sharply at
. IbandIcjump from underto about in that one step. - Nothing whatsoever happens at
. The trace runs straight through it. A balanced fault on a balanced line produces no zero-sequence current, so the ground mode is never excited — there is no second arrival to see. at every step, to numerical precision. That is the same statement as point 2, read in the phase domain instead of the modal one.
To unbalance the fault, open the fault component, change Fault type to A-G (1φ to gnd), then re-run and zoom in the same way:
- A second arrival appears at
. The first break remains at , but the trace now kinks again sixty microseconds later. A single fault arrives twice, because the energy it launched has split between two modes travelling at different speeds. The second arrival lands at rather than , so the predicted rounding is directly measurable. - Phases B and C respond, although the fault touched only phase A and nothing was ever connected to B or C. Their peaks grow by tens of percent over the cycle that follows. This is the coupling that the off-diagonal terms of
and describe. - The fault current is much smaller, with a peak near
against for the balanced case. A single-phase-to-ground fault must drive current through the zero-sequence path, and is twenty times . The ground mode is the bottleneck.
The two modes can be separated further by setting
The balanced run repays one further observation. The sending-end currents do not jump to a final value and remain there; they climb in a staircase of roughly
10.7 Summary
- On a multiconductor line the per-unit-length parameters are matrices, and their off-diagonal terms couple the phases so tightly that no single surge impedance or travel time exists.
- Diagonalizing
produces modes — combinations of phase quantities that propagate independently, each as an ordinary Chapter 8 line with its own and . - On a balanced line the eigenvectors are Clarke's, real and constant and independent of the parameter values, and the modes split into one ground mode (
, earth return) and two degenerate aerial modes (currents summing to zero). - Physically, the earth return makes
and , hence and : the ground mode is slower and higher-impedance, and it arrives second. - NumaSim accepts sequence surge impedances, sequence RLC, or self/mutual matrix data, reducing all three to
. Matrix entry cannot express ; sequence RLC can. - Each half-line stamps the coupled Norton equivalent as three grounded conductances plus three phase-to-phase branches, and delays the two mode families independently,
and steps.
10.8 Problems
Problem 10.1. A balanced line has
Solution 10.1
Apply the eigenvalue reductions:
Surge impedances:
Travel times over
Sanity checks:
Problem 10.2. For the line of Problem 10.1, what is the largest time step at which it still runs as a travelling-wave line, and how many steps of delay does each mode get at
Solution 10.2
The fallback test uses the smaller travel time, which is always the aerial mode's. So the line stays distributed as long as
At
Both are within about 5 %, consistent with the
Problem 10.3. A single conductor of a three-phase line is energized while the other two are open. Which modes are excited, and what does the far end see?
Solution 10.3
Both. A phase-A-only excitation is
Because the two mode families travel at different speeds, the far end sees the disturbance twice: an aerial-mode arrival at
This is precisely why single-pole switching is a distinct study from three-pole switching, and why line energization is analyzed in the modal domain.
Problem 10.4. Your datasheet gives
Solution 10.4
The surge impedances transfer directly. The travel times come from length over velocity:
The entries are therefore
Problem 10.5. Why can a fully transposed line be diagonalized by a real, constant matrix while a general untransposed line cannot?
Solution 10.5
Transposition makes all three conductors electrically interchangeable, so every matrix in the problem is symmetric and invariant under any permutation of the three phases. A matrix with that symmetry necessarily has the form
An untransposed line has three genuinely different conductor positions, so its matrices lose the permutation symmetry. The eigenvectors then depend on the actual entries, which are frequency-dependent and complex, so the transformation becomes complex and frequency-dependent too. Practical models handle this by fitting a constant real transformation over the frequency band of interest and accepting the error, which is why transposed data is so much easier to work with.
Problem 10.6. Matrix data is available for a line whose zero-sequence resistance is four times its positive-sequence resistance. How should it be entered?
Solution 10.6
Not through the balanced-matrix entry, which takes a single
The data should be converted to sequence quantities by hand —
10.9 References
- E. Clarke, Circuit Analysis of A-C Power Systems, Wiley — the
transformation used here for the balanced case. - L. M. Wedepohl, "Application of matrix methods to the solution of travelling-wave phenomena in polyphase systems", Proc. IEE, 1963 — modal decomposition of multiconductor lines.
- H. W. Dommel, Electromagnetic Transients Program (EMTP) Theory Book, Bonneville Power Administration — modal travelling-wave line models.
- J. Arrillaga and N. R. Watson, Power Systems Electromagnetic Transients Simulation, IET Power and Energy Series 39 — multiconductor lines and the eigenvalue/eigenvector formulation.
Previous: Chapter 9 — Losses, lumped lines, and the time step · Next: Chapter 11 — Frequency-dependent line models.