Appearance
Chapter 19 — Governors, turbines, and stabilizers
Chapter 18 closed one of the machine's two loops. The exciter controls the field, and through it the terminal voltage. This chapter closes the other one. The governor controls the valve, and through it the mechanical torque on the shaft — and therefore the speed, and therefore the system frequency.
Then it adds a third element that belongs to neither loop and improves both: the power system stabilizer, a small supplementary signal injected into the exciter that damps the rotor oscillations a high-gain AVR would otherwise aggravate.
Learning objectives
By the end of this chapter you should be able to:
- Explain why generators are governed with droop rather than to a fixed frequency, and compute the steady-state frequency and power sharing that droop produces.
- Trace the TGOV1 block diagram and write the difference equation each stage becomes.
- Explain what a load limiter, an acceleration limiter and a low-value select do in a modern governor, and why the PID needs anti-windup.
- Explain why a high-gain AVR can reduce damping torque, and how a stabilizer fixes it without disturbing the voltage set-point.
- Say why every stabilizer starts with a washout, and what phase compensation is compensating for.
- Predict whether a governor will visibly respond to a disturbance, given the stiffness of the system it is connected to.
19.1 Speed control and droop
The swing equation from Chapter 15 says the rotor accelerates whenever the mechanical torque exceeds the electrical torque:
Electrical torque is set by the load; the only controllable term is
The obvious control law is isochronous: integrate the speed error and drive it to exactly zero, holding frequency at precisely 60 Hz. It works beautifully for one machine alone. Put two isochronous machines on the same grid and it fails immediately — both are trying to set the same frequency, and any tiny mismatch in their measurements sends one to full load and the other to zero as each fights to impose its own set-point. There is no stable division of load between them.
The universal fix is droop: deliberately make the governor accept a frequency error proportional to its output. With a permanent droop
so each machine picks up load in proportion to
This is why grid frequency droops under load and is later restored by a slower, system-wide process (automatic generation control) that shifts the governors' references rather than fighting them. Droop is the fast, autonomous, proportional layer; frequency restoration is the slow, coordinated, integral layer on top.
19.2 The TGOV1
TGOV1 is the minimal credible steam turbine-governor: a droop, a valve lag, a reheat lead-lag, and an optional damping term. It is defined in IEEE PES-TR1, and it is the model to reach for when you want the effect of governing without committing to a specific plant.
Stage by stage, with the update each becomes:
Droop.
Governor / valve lag
Turbine lead-lag
Damping
Torque conversion. The machine's swing equation takes torque, but the turbine produces power, and
19.3 The GGOV1
TGOV1 is a caricature. GGOV1 is what a modern governor actually looks like, and it is worth studying not because you will hand-tune all thirty of its parameters but because its structure recurs in every real plant controller.
Four ideas beyond TGOV1:
Selectable droop feedback. TGOV1 always droops on speed. GGOV1's Rselect chooses what the droop signal is measured from: electrical power (the default, and the most common in practice), valve stroke, governor output, or nothing at all — the last giving isochronous control, which is exactly what you want for a single machine running an island.
A PID, with anti-windup that back-calculates. The speed error drives
Low-value select. Three controllers compete for the valve: the speed governor, an acceleration limiter (which caps
This is the standard way to compose limiters in prime-mover control: whoever is most conservative wins, automatically and without mode-switching logic.
A rate-limited actuator. The valve cannot slam. Ropen and Rclose bound how fast the stroke may change per second, and only then is the position clamped to
Two smaller features complete the picture: Flag makes fuel flow proportional to speed (right for a mechanically-driven fuel system), and Teng is a transport delay for engine combustion, realized as the integer-sample ring buffer of §17.2.
19.4 Why a stabilizer is needed
Here is the uncomfortable fact that motivates the third controller. A high-gain, fast-acting AVR — the very thing Chapter 18 argued for — reduces the damping of rotor oscillations.
The mechanism, briefly. Following a disturbance the rotor swings against the system, and the machine's electrical torque can be resolved into two components: a synchronizing component in phase with the angle deviation
A fast AVR is superb at supplying synchronizing torque — that is exactly the field forcing you watched in Lab 18.7. But the exciter and field circuit together introduce phase lag, and by the time the AVR's response reaches the air gap it can be far enough behind the rotor's motion to appear as negative damping at the natural oscillation frequency of about 0.2 to 2 Hz. The result is a machine that holds voltage well and hunts, with a slowly growing swing that the AVR itself is feeding.
The remedy is not to detune the AVR — that would give up the synchronizing torque you need. It is to add a supplementary signal to the AVR's summing junction that is deliberately shaped to produce torque in phase with speed. That signal is
19.5 PSS1A and STAB1
Both stabilizers in the library take the machine's speed and return
A washout, always first in spirit. The stage
The time constant is long — 10 s by default — because the washout must pass oscillations at 0.2 Hz while rejecting the slow frequency drift that governors are handling.
Phase compensation. Two lead-lag stages
Gain and limit.
The two models differ mainly in packaging. PSS1A is the IEEE 421.5 model and adds an optional second-order input filter
Where the gain sits
In NumaSim's PSS1A the stabilizer gain vw monitoring signal, which reports the washout output before the gain is applied. If you are comparing vw against a hand calculation, do not multiply by
19.6 Initializing the governor
The governor's initialization is the same idea as the exciter's in §18.6, and mercifully simpler.
At the operating point the machine runs at synchronous speed, so
The load reference is the scheduled mechanical power. The pairing works exactly as the exciter's does — the governor's Tm output is traced through the resolved connection graph to the machine whose Tm input it drives — and the same warnings apply if the trace fails.
GGOV1 needs one extra number because its droop feeds back from electrical power rather than speed: with Rselect = 1 the steady state requires
Two caveats worth knowing. On a multi-mass shaft, the machine has several torque inputs
19.7 Lab: a governor that barely moves, and why that is correct
Open the generator controls disturbance in simulator →
(Full description: generator controls disturbance.)
The same circuit as Lab 18.7, now read from the governor's side. The machine carries a TGOV1 with
Plot Pmech and the valve position through the disturbance. Across the whole event, Pmech moves by 0.002 pu and the valve by 0.006 — which is to say, essentially nothing, while the AVR next to it swung its output by 1.1 pu.
That is not a broken governor. It is the single most important thing this lab teaches, and the reasoning is worth doing carefully:
- A droop governor responds only to speed error.
- The machine is connected to a 500 MVA system source, five times its own rating.
- A source that stiff holds the bus frequency essentially constant, whatever the 100 MVA machine does.
- So the speed error never really develops.
- So the governor has nothing to act on.
The disturbance is the AVR's to handle, and it handles it. Voltage collapses and the exciter responds; frequency does not move and the governor does not. Which controller responds to a disturbance is decided by the disturbance, not by the controller — and a fault on a stiff bus is a voltage event, not a frequency event.
Now make the governor matter. Weaken the source — raise its impedance until its short-circuit capacity is comparable with the machine's rating — or island the machine with its load entirely. Re-run and watch Pmech and the speed. Now the machine's own inertia sets the frequency, a load change moves it, and the droop governor picks up load in proportion to R from 0.05 to 0.02 and confirm the steady-state frequency deviation shrinks by the same factor; and shorten T3 toward T2 to watch the reheat lag disappear and the mechanical power arrive all at once.
19.8 Summary
- Generators are governed with droop, not to a fixed frequency, because two isochronous machines on one grid cannot share load stably. Droop makes frequency the shared signal that divides load in proportion to
. - TGOV1 is droop, a non-windup valve lag, a reheat lead-lag whose immediate response is only
of its final value, an optional damping term, and a division by to convert power to torque. - GGOV1 adds selectable droop feedback, a PID with back-calculated anti-windup, a low-value select against acceleration and load limiters, and a rate-limited actuator.
- A high-gain AVR supplies synchronizing torque but can supply negative damping at rotor-oscillation frequencies. A stabilizer fixes this by injecting
shaped to produce torque in phase with . - Every stabilizer begins with a washout, so
is exactly zero in steady state and adding one never shifts the voltage set-point. The lead-lag stages compensate for the phase lag of the exciter and field circuit. - Governor initialization back-calculates
from the load-flow operating point. A mis-initialized governor makes power drift with no disturbance; a mis-initialized exciter makes voltage drift. - Whether a governor visibly responds depends on the stiffness of the system. On a bus held by a much larger source, a fault is a voltage event and the governor correctly does almost nothing.
19.9 Problems
Problem 19.1. Two generators share an island. Unit A is 200 MVA with
Solution 19.1
Work in MW per per-unit frequency. Each unit's contribution is
- A:
MW/pu - B:
MW/pu
Total stiffness
Sharing: A picks up
Note that B, though half A's size, takes more than half of A's share, because its tighter droop makes it stiffer per MVA.
Problem 19.2. A TGOV1 has
Solution 19.2
A lead-lag
Immediately after the step:
This is the reheat characteristic of a steam turbine. Opening the valve immediately admits more steam to the high-pressure stage, which delivers about 30 % of the unit's output; the rest of the steam must pass through the reheater before it reaches the intermediate- and low-pressure stages, and the reheater's thermal storage is what sets the 7-second lag. It is the reason steam units are poor at fast frequency response compared with hydro or gas.
Problem 19.3. Explain the difference between the DC1A's output clamp and GGOV1's back-calculated anti-windup. Construct a case where the difference is visible.
Solution 19.3
The DC1A clamps the regulator's integrator state to the limit. The state is therefore never outside the limit, and the output leaves the limit as soon as the input reverses. GGOV1 integrates first, then computes the controller output
The difference shows up when the controller has a proportional path in parallel with the integrator, which GGOV1 does and the DC1A's simple lag does not. Suppose the output is pinned at
With a pure lag and no parallel path, as in the DC1A, the two schemes coincide.
Problem 19.4. A colleague proposes to eliminate the washout from a stabilizer, arguing that its DC gain of zero "throws away information." Explain what would go wrong, both in steady state and at initialization.
Solution 19.4
In steady state, the stabilizer would output
At initialization it is worse. §18.6's back-calculation computes
The washout is not throwing information away; it is discarding precisely the component of the signal (the DC value) that the stabilizer has no business acting on. The stabilizer's job is to damp oscillations, and oscillations are what remains after the DC value is removed.
Problem 19.5. In Lab 19.7 the governor barely moves, while in a different study of the same machine it responds strongly. What changed? Give two distinct system conditions that would make the governor the dominant responder, and one disturbance type that would engage the governor but not the AVR.
Solution 19.5
What changed is the stiffness of the system the machine is connected to, not anything about the governor. A droop governor acts on speed error, and speed error only develops if the machine's own power imbalance is large enough to move the frequency.
Two conditions that make the governor dominant: (a) islanding the machine with its load, so its own inertia alone sets the frequency; (b) weakening the external source until its short-circuit capacity is comparable with the machine's rating, so the machine participates meaningfully in frequency regulation.
A disturbance that engages the governor but not the AVR: a load step in an island — say, switching in a large motor. Frequency dips, the governor opens the valve, and the terminal voltage barely moves if the load is largely real power near the machine. The complement is the lab's own case, a bolted fault on a stiff bus: pure voltage event, no frequency event.
Problem 19.6. You attach a stabilizer to a machine, run without a power flow, and see the terminal voltage drift for the first two seconds. Is the stabilizer the cause? Explain how you would isolate it.
Solution 19.6
Almost certainly not. A stabilizer's washout is seeded so that
The likely cause is that the exciter was not initialized — that is what running without a power flow does. Its
To isolate it: disconnect the stabilizer's
19.10 References
- IEEE PES-TR1, Dynamic Models for Turbine-Governors in Power System Studies, IEEE Power & Energy Society — the source of the TGOV1 and GGOV1 models.
- IEEE Std 421.5, IEEE Recommended Practice for Excitation System Models for Power System Stability Studies, Clause 9 — the PSS1A and the stabilizer family.
- P. Kundur, Power System Stability and Control, McGraw-Hill — Chapter 9 for prime movers and speed governing, Chapter 12 for small-signal stability, the decomposition into synchronizing and damping torque, and PSS tuning.
- IEEE Committee Report, "Dynamic models for steam and hydro turbines in power system studies," IEEE Transactions on Power Apparatus and Systems, 1973 — the origin of the reheat turbine representation.
- E. V. Larsen and D. A. Swann, "Applying power system stabilizers, Parts I-III," IEEE Transactions on Power Apparatus and Systems, vol. PAS-100, no. 6, 1981 — the standard treatment of PSS phase compensation and tuning.
Previous: Chapter 18 — Excitation systems and AVRs · Next: Module 6 — System studies.