Rate Limiter ​

Limits how fast a double signal may change. Each step the output moves toward the input by at most rising rate × Δt upward and falling rate × Δt downward (rates are positive magnitudes, in units per second or per minute). Use it for ramped set-points, load-reference ramps and slew-limited actuators. By default the output starts at the first input value (bumpless); it can instead start from a fixed initial value and ramp from there.

Category: Nonlinear

Ports ​

PortKindSignalNotes
inControl inputReal
outControl outputReal

Parameters ​

ParameterTypeDefaultUnitsDescriptionID
Rising rateNumber1/s (also /min)Largest allowed increase per unit time (positive magnitude; the sign is ignored).rising_rate
Falling rateNumber1/s (also /min)Largest allowed decrease per unit time (positive magnitude; the sign is ignored).falling_rate
Start fromChoice: First input (bumpless) / Initial valueFirst input (bumpless)—First input = the output equals the input on the first step (bumpless). Initial value = the output starts at Initial value and ramps toward the input.init_mode
Initial valueNumber0—Output value before the first step when Start from = Initial value.initial_value

In the course ​