Ideal Transformer (3-phase) ​

Three-phase ideal two-winding (HV / LV) transformer: no leakage, no magnetizing branch, no losses. Enforces V_LV,LL = V_HV,LL / n with n the line-to-line voltage ratio, for any Y / YN / Δ connection on each side and an exact HV→LV vector-clock phase shift (even clocks for Yy / Dd, odd clocks for Yd / Dy). A YN star point is either grounded internally or brought out to an HV_n / LV_n port. Per-phase HV and LV line currents can be monitored with a '+ve in' / '+ve out' sign convention. A grounded wye facing a delta is an ideal zero-sequence short, so do not drive that winding from an ideal source with a grounded neutral (give the source some impedance or a floating neutral). Use for level-shifting, phase-shifting, and isolation in three-phase studies where the transformer impedance does not matter.

Category: Transformers

Ports ​

PortKindSignalNotes
HVThree-phase terminal—
LVThree-phase terminal—
HV_nElectrical terminal—Shown when HV connection is YN (wye + neutral) and HV neutral is Neutral exposed (HV_n port)
LV_nElectrical terminal—Shown when LV connection is yn (wye + neutral) and LV neutral is Neutral exposed (LV_n port)

Parameters ​

Config ​

ParameterTypeDefaultUnitsDescriptionID
n (HV:LV, line-to-line)Number1—Line-to-line voltage ratio V_HV,LL : V_LV,LL = n : 1 (e.g. 230 kV : 115 kV is n = 2). The per-winding turns ratio follows from the connections: n for Yy and Dd, n/√3 for Yd, n·√3 for Dy.turns_ratio
HV connectionChoice: Y (floating N) / YN (wye + neutral) / Δ deltaYN (wye + neutral)—HV winding connection. `Y` = wye with a floating (isolated) neutral. `YN` = wye with an accessible neutral; the `HV neutral` selector below decides whether it is grounded internally or brought out to the HV_n port. `D` = delta (winding a spans phases a→b).hv_connection
HV neutralChoice: Neutral exposed (HV_n port) / Grounded internallyGrounded internally—How the HV star point is handled (YN only). `Exposed`: brought out to the HV_n port — ground it externally or connect an impedance. `Grounded`: solidly tied to ground inside the transformer (no HV_n port).hv_neutral
LV connectionChoice: y (floating n) / yn (wye + neutral) / d (delta)yn (wye + neutral)—LV winding connection. `y` = wye with a floating (isolated) neutral. `yn` = wye with an accessible neutral; the `LV neutral` selector below decides whether it is grounded internally or brought out to the LV_n port. `d` = delta (winding a spans phases a→b).lv_connection
LV neutralChoice: Neutral exposed (LV_n port) / Grounded internallyGrounded internally—How the LV star point is handled (yn only). `Exposed`: brought out to the LV_n port. `Grounded`: solidly tied to ground inside the transformer (no LV_n port).lv_neutral
HV→LV vector clockChoice: 0 (in phase) / 2 (−60°) / 4 (−120°) / 6 (180°) / 8 (+120°) / 10 (+60°)0 (in phase)—Phase shift of LV relative to HV in 30° clock units (LV lags HV by 30° × clock). Yy and Dd connections admit only even clocks.hv_lv_clock_even
HV→LV vector clockChoice: 1 (−30°) / 3 (−90°) / 5 (−150°) / 7 (+150°) / 9 (+90°) / 11 (+30°)1 (−30°)—Phase shift of LV relative to HV in 30° clock units (LV lags HV by 30° × clock). Yd and Dy connections admit only odd clocks, e.g. YNd1, Dyn11.hv_lv_clock_odd
Current monitoring - HV sideChoice: Off / OnOff—Emit the per-phase HV line currents (at the HV terminals) as simulator observables.measure_hv_current
HV positive directionChoice: +ve in / +ve out+ve in—Sign convention for the monitored HV line currents. '+ve in' = positive when current flows into the transformer at the HV terminal; '+ve out' = positive when it flows out.hv_current_dir
Current monitoring - LV sideChoice: Off / OnOff—Emit the per-phase LV line currents (at the LV terminals) as simulator observables.measure_lv_current
LV positive directionChoice: +ve in / +ve out+ve out—Sign convention for the monitored LV line currents. '+ve in' = positive when current flows into the transformer at the LV terminal; '+ve out' = positive when it flows out (the default, so power delivered to an LV load reads positive).lv_current_dir

Current Monitoring ​

ParameterTypeDefaultUnitsDescriptionID
HV name ATextI_HVa—Signal name for the Phase A HV line current. Blank skips this phase; change the default when you have several monitored transformers — duplicate ids collide.i_hv_name_a
HV name BTextI_HVb—Signal name for the Phase B HV line current. Blank skips this phase.i_hv_name_b
HV name CTextI_HVc—Signal name for the Phase C HV line current. Blank skips this phase.i_hv_name_c
LV name ATextI_LVa—Signal name for the Phase A LV line current. Blank skips this phase.i_lv_name_a
LV name BTextI_LVb—Signal name for the Phase B LV line current. Blank skips this phase.i_lv_name_b
LV name CTextI_LVc—Signal name for the Phase C LV line current. Blank skips this phase.i_lv_name_c

Observables ​

Default nameKindRecorded whenDescriptionID
set by HV name ASignalCurrent monitoring - HV side is onPhase A HV line current (A). Positive into the HV_a terminal for '+ve in' (default), out of it for '+ve out'.i_HV_a
set by HV name BSignalCurrent monitoring - HV side is onPhase B HV line current (A).i_HV_b
set by HV name CSignalCurrent monitoring - HV side is onPhase C HV line current (A).i_HV_c
set by LV name ASignalCurrent monitoring - LV side is onPhase A LV line current (A). Positive out of the LV_a terminal for '+ve out' (default), into it for '+ve in'.i_LV_a
set by LV name BSignalCurrent monitoring - LV side is onPhase B LV line current (A).i_LV_b
set by LV name CSignalCurrent monitoring - LV side is onPhase C LV line current (A).i_LV_c