Skip to content

Wind Turbine ​

Variable-pitch wind turbine rotor: steady-state aerodynamic power from wind speed, generator speed and blade pitch, delivered as shaft torque in pu of the generator. Mechanical power is P = kp·(Cp/Cpmax)·(v/vbase)³ pu of the nominal power, with the generic performance coefficient Cp(λ, β) = c1(c2/λi − c3β − c4)e^(−c5/λi) + c6λ and 1/λi = 1/(λ + 0.08β) − 0.035/(β³ + 1); the tip-speed ratio is λ = λnom·(ω/ωbase)/(v/vbase), where λnom is the ratio at which Cp(λ, 0) peaks. Torque is Tm = P·Pnom/(Sgen·ω). A power-limiting pitch controller (PI on P − Plim with anti-windup, then a rate-limited servo) raises the pitch above rated power and rests on the minimum pitch below it; a fixed-pitch mode holds a constant angle. The rotor inertia is not inside: wire Tm to the synchronous or induction machine shaft (a two-mass shaft puts it on the turbine mass) and the machine speed back to the speed input. Use it as the prime mover of a Type-3 or Type-4 wind turbine.

Category: Control / Turbine

Overview ​

The Wind Turbine block is the aerodynamic rotor of a variable-speed wind turbine. It reads the wind speed and the generator rotor speed and outputs the mechanical torque that drives the generator, together with the blade pitch angle.

The rotor power follows the standard power-coefficient curve Cp(λ,β), and a pitch controller sheds power above rated wind. Pair it with a Synchronous Machine (Type-4 full-converter turbine) or an Induction Machine: wire the machine's speed output to ω and the block's Tm to the machine's Tm input.

Power coefficient ​

The power coefficient is the generic six-constant curve

Cp(λ,β)=c1(c2λi−c3β−c4)e−c5/λi+c6λ,1λi=1λ+0.08β−0.035β3+1,

with β in degrees. The defaults (c1…c6=0.5176, 116, 0.4, 5, 21, 0.0068) peak at Cp,max≈0.48 at λnom≈8.1 with zero pitch. The block locates the peak of whatever constants you enter, so the per-unit scaling below stays consistent when you change them.

Per-unit rotor model ​

All quantities are per unit: wind on the base wind speed, speed on the base rotor speed, and power on the nominal mechanical powerPnom.

vpu=vvbase,λ=λnomω/ωbasevpu,Ppu=kpCp(λ,β)Cp,maxvpu3.

kp (power gain) is the power, in pu of Pnom, at base wind on the optimum tip-speed ratio. The torque is delivered on the generator's own base Sgen:

Tm=PpuPnomSgenω.

When Pnom=Sgen and ω=1, Tm=Ppu. Zero (or negative) wind gives zero torque.

Pitch control ​

With Pitch mode = Power limiting a PI controller acts on the power error Ppu−Plimit. Its command is clamped to [βmin,βmax] (the integrator is held so the command does not wind up past the clamp). A first-order servo with time constant Tservo and a rate limit then moves the blades. Below rated wind the error is negative and the pitch rests on βmin. Above rated wind the pitch rises until the power is back at Plimit.

Pitch mode = Fixed holds β at Fixed pitch and skips the controller.

The pitch starts at Initial pitch. Start it near the expected operating pitch to avoid a power overshoot at the beginning of a run.

Example operating point ​

With base wind 11 m/s, base speed 1 pu and kp=0.8, a 15 m/s wind at 1 pu speed settles at 1 pu power on a pitch of 8.8°.

Wiring ​

  • v ← wind speed (m/s), for example a Constant or a Time Table for gusts and ramps.
  • ω ← the machine's speed output (pu).
  • Tm → the machine's Tm input (pu on the machine base).
  • β → optional, for plotting or downstream logic (degrees).

Enable the options on the Monitoring tab to record the mechanical power, the pitch, and Cp as named signals.

Ports ​

PortKindSignalNotes
windControl inputReal
speedControl inputReal
TmControl outputReal
pitchControl outputReal

Parameters ​

Turbine ​

ParameterTypeDefaultUnitsDescriptionID
PnomNumber2MW (also W, kW)Nominal mechanical output power of the turbine. The mechanical power P is in pu of this value.p_nom
SgenNumber2MVA (also VA, kVA)Rated power of the generator the turbine drives. The torque output is in pu of that machine's rated torque, so it wires straight to the machine's Tm input.s_gen
Base wind speedNumber12m/s (also km/h)Base wind speed of the per-unit system. At this wind speed and the base rotational speed, with zero pitch, the turbine delivers the power gain kp.base_wind
kp (power at base wind)Number0.73—Maximum power at the base wind speed, in pu of the nominal power (≤ 1).power_gain
Base rotational speedNumber1.2—Generator speed (pu of synchronous speed) at which the turbine reaches its maximum power at the base wind speed, i.e. where λ = λnom.base_speed

Pitch ​

ParameterTypeDefaultUnitsDescriptionID
PitchChoice: Power limiting / FixedPower limiting—Power limiting = a PI on the power error raises the pitch when the power exceeds Plim and rests on the minimum pitch below it. Fixed = hold the pitch at the fixed angle.pitch_mode
Fixed pitchNumber0° (also rad)Blade pitch held in Fixed mode.pitch_fixed
PlimNumber1—Power the pitch controller limits to, in pu of the nominal power.p_limit
KpNumber10—Proportional gain of the pitch controller, degrees per pu of power error.kp_pitch
KiNumber20—Integral gain of the pitch controller, degrees per pu-second of power error.ki_pitch
βminNumber0° (also rad)Minimum pitch. The controller rests here below rated power.pitch_min
βmaxNumber45° (also rad)Maximum pitch.pitch_max
Rate limitNumber10°/s (also rad/s)Largest pitch speed of the servo, either direction.pitch_rate
Servo time constantNumber0.1s (also ms)Time constant of the first-order pitch servo. 0 makes the servo follow the command at the rate limit.t_servo
Initial pitchNumber0° (also rad)Pitch, and the controller integrator, at t = 0. Set it to the expected operating pitch to start above rated wind without a power overshoot.pitch0

Cp ​

ParameterTypeDefaultUnitsDescriptionID
c1Number0.5176—Coefficient c1 of Cp(λ, β) = c1(c2/λi − c3β − c4)e^(−c5/λi) + c6λ.c1
c2Number116—Coefficient c2 of the performance coefficient.c2
c3Number0.4—Coefficient c3 of the performance coefficient (per degree of pitch).c3
c4Number5—Coefficient c4 of the performance coefficient.c4
c5Number21—Coefficient c5 of the performance coefficient.c5
c6Number0.0068—Coefficient c6 of the performance coefficient.c6

Monitoring ​

ParameterTypeDefaultUnitsDescriptionID
Monitor powerChoice: Off / OnOff—Record the aerodynamic power P (pu of Pnom) as a named observable.measure_power
Monitor pitchChoice: Off / OnOff—Record the blade pitch (degrees) as a named observable.measure_pitch
Monitor CpChoice: Off / OnOff—Record the performance coefficient Cp as a named observable.measure_cp

Signal Names ​

ParameterTypeDefaultUnitsDescriptionID
Power nameText(empty)—Observable name for the aerodynamic power. Blank = skip.power_name
Pitch nameText(empty)—Observable name for the blade pitch. Blank = skip.pitch_name
Cp nameText(empty)—Observable name for the performance coefficient. Blank = skip.cp_name

Observables ​

Default nameKindRecorded whenDescriptionID
set by Power nameSignalMonitor power is onAerodynamic power P = kp·(Cp/Cpmax)·(v/vbase)³, pu of the nominal power.pmech
set by Pitch nameSignalMonitor pitch is onBlade pitch β in degrees, after the servo and rate limit.pitch
set by Cp nameSignalMonitor Cp is onPerformance coefficient Cp(λ, β) at the present tip-speed ratio and pitch.cp