Transmission Line Type
The data a Transmission Line uses: single- or three-phase, PI or Bergeron, entered as surge impedance, per-length RLC, sequence data or a balanced matrix, plus a default length. Types are stored with the circuit and edited from the Line types panel, not placed on the canvas; every Transmission Line that references a type follows its edits.
Category: Transmission
Ports
This component has no wired ports.
Parameters
Config
| Parameter | Type | Default | Units | Description | ID |
|---|---|---|---|---|---|
| Conductors | Choice: 1 / 3 | 1 | — | Number of conductors. 1 = single-phase (one electrical node per terminal); 3 = three-phase (one electrical_3ph node per terminal). More counts are future work. | number_of_conductors |
| Data entry | Choice: Bergeron — Surge Impedance / Bergeron — RLC / PI — RLC / Physical (coming soon) | Bergeron — Surge Impedance | — | How the single-phase line is parameterized. Bergeron entries give a travelling-wave model; PI gives a lumped nominal-pi section. All forms reduce to the same canonical R/L/C. | data_entry_1ph |
| Data entry | Choice: Bergeron — Sequence Surge Impedance / Bergeron — Sequence RLC / Bergeron — Balanced Matrix / PI — Sequence RLC / PI — Balanced Matrix / Physical (coming soon) | Bergeron — Sequence Surge Impedance | — | How the three-phase line is parameterized. Sequence / matrix data is reduced to positive- and zero-sequence canonical R/L/C. | data_entry_3ph |
| Length (km) | Number | 100 | — | Default line length in km. Per-length data is multiplied by it; a placed Transmission Line can override it. | length |
Bergeron Parameters
| Parameter | Type | Default | Units | Description | ID |
|---|---|---|---|---|---|
| Zc (Ω) | Number | 400 | — | Surge / characteristic impedance. | zc |
| τ (travel time) | Number | 100 | µs (also s, ms) | One-way travel time of the line. | tau |
RLC Parameters
| Parameter | Type | Default | Units | Description | ID |
|---|---|---|---|---|---|
| R | Number | 0.05 | Ω/km (also Ω/m, pu/km) | Series resistance per unit length. Choose pu/km to enter book per-unit data (e.g. Kundur r); the value is converted with Z_base = V_base² / S_base from the Units tab. | r_per_len |
| L | Number | 0.000001 | H/m (also H/km, mH/km, µH/km, pu/km) | Series inductance per unit length (default 1e-6 H/m = 1 mH/km). With pu/km the value is read as series reactance per km (book xL) in per-unit: L = x·Z_base / (2π·Freq). | l_per_len |
| C | Number | 1e-11 | F/m (also F/km, mF/km, µF/km, pu/km) | Shunt capacitance per unit length (default 1e-11 F/m = 0.01 µF/km). With pu/km the value is read as shunt susceptance per km (book bc) in per-unit: C = b / (Z_base·2π·Freq). | c_per_len |
Sequence Surge Impedance
| Parameter | Type | Default | Units | Description | ID |
|---|---|---|---|---|---|
| Z1 (Ω) | Number | 350 | — | Positive-sequence surge impedance. | z1 |
| τ1 (travel time) | Number | 100 | µs (also s, ms) | Positive-sequence one-way travel time. | tau1 |
| Z0 (Ω) | Number | 550 | — | Zero-sequence surge impedance. | z0 |
| τ0 (travel time) | Number | 130 | µs (also s, ms) | Zero-sequence one-way travel time. | tau0 |
Sequence RLC
| Parameter | Type | Default | Units | Description | ID |
|---|---|---|---|---|---|
| R1 | Number | 0.03 | Ω/km (also Ω/m, pu/km) | Positive-sequence series resistance per unit length. Choose pu/km to enter book per-unit data (e.g. Kundur r); converted with Z_base = V_base² / S_base from the Units tab. | r1_per_len |
| L1 | Number | 9e-7 | H/m (also H/km, mH/km, µH/km, pu/km) | Positive-sequence series inductance per unit length (default 9e-7 H/m = 0.9 mH/km). With pu/km the value is read as positive-sequence series reactance per km (book xL) in per-unit: L1 = x·Z_base / (2π·Freq). | l1_per_len |
| C1 | Number | 1.2e-11 | F/m (also F/km, mF/km, µF/km, pu/km) | Positive-sequence shunt capacitance per unit length (default 1.2e-11 F/m = 0.012 µF/km). With pu/km the value is read as positive-sequence shunt susceptance per km (book bc) in per-unit: C1 = b / (Z_base·2π·Freq). | c1_per_len |
| R0 | Number | 0.3 | Ω/km (also Ω/m, pu/km) | Zero-sequence series resistance per unit length. Choose pu/km to enter book per-unit data; converted with Z_base = V_base² / S_base from the Units tab. | r0_per_len |
| L0 | Number | 0.0000026 | H/m (also H/km, mH/km, µH/km, pu/km) | Zero-sequence series inductance per unit length (default 2.6e-6 H/m = 2.6 mH/km). With pu/km the value is read as zero-sequence series reactance per km in per-unit: L0 = x·Z_base / (2π·Freq). | l0_per_len |
| C0 | Number | 8e-12 | F/m (also F/km, mF/km, µF/km, pu/km) | Zero-sequence shunt capacitance per unit length (default 8e-12 F/m = 0.008 µF/km). With pu/km the value is read as zero-sequence shunt susceptance per km in per-unit: C0 = b / (Z_base·2π·Freq). | c0_per_len |
Balanced Matrix
| Parameter | Type | Default | Units | Description | ID |
|---|---|---|---|---|---|
| Rs (Ω) | Number | 3 | — | Total per-phase series resistance (self) at the type's default length. A placed line that overrides the length scales it in proportion. | rs_ohm |
| Ls | Number | 0.0000015 | H/m (also H/km, mH/km, µH/km) | Self inductance per unit length (diagonal of L matrix; default 1.5e-6 H/m = 1.5 mH/km). | ls_per_len |
| Lm | Number | 5.7e-7 | H/m (also H/km, mH/km, µH/km) | Mutual inductance per unit length (off-diagonal of L matrix; default 5.7e-7 H/m = 0.57 mH/km). L1 = Ls − Lm, L0 = Ls + 2·Lm. | lm_per_len |
| Cs | Number | 1.1e-11 | F/m (also F/km, mF/km, µF/km) | Self capacitance per unit length (diagonal of Maxwell C matrix; default 1.1e-11 F/m = 0.011 µF/km). | cs_per_len |
| Cm | Number | 1e-12 | F/m (also F/km, mF/km, µF/km) | Mutual capacitance per unit length (magnitude of off-diagonal; default 1e-12 F/m = 0.001 µF/km). C1 = Cs + Cm, C0 = Cs − 2·Cm. | cm_per_len |
Units
| Parameter | Type | Default | Units | Description | ID |
|---|---|---|---|---|---|
| S_base (MVA) | Number | 100 | — | System base apparent power in MVA. Used by `pu` impedance / admittance conversions in this component's `computations` block. | S_base |
| V_base (kV) | Number | 230 | — | Base RMS line-to-line voltage in kV. Used by `pu` impedance / admittance conversions in this component's `computations` block. | V_base |
| Frequency (Hz) | Number | 60 | — | Frequency in Hz. Used by `B` (susceptance) / `X` (reactance) conversions in this component's `computations` block. | Freq |